Wire Size Calculator (sq mm) for House Wiring
Find the copper wire size in sq mm for a load and distance, single or three phase, checked for current, voltage drop and the usual minimum per circuit, with the MCB.
Assumptions used EDIT ▾
3% is a common limit.
Ratings are conservative values for PVC-insulated copper house wire, two wires in a conduit; wires bunched together, hot roofs or long runs need a bigger size. The wire must carry the current plus 25% and keep voltage drop under the limit. Always follow the wire maker's rating table and have a licensed electrician check the circuit.
COPPER WIRE
2.5sq mm
Chosen for the usual minimum for this circuit
- CurrentWire rating 18 A
- 8.7 A
- Voltage drop1.1% of 230 V
- 2.5 V
- MCBProtects the wire; never larger than its rating
- 10 A
How it’s calculated
I = W ÷ (230 × pf); choose the smallest wire rated ≥ I × 1.25 with voltage drop 2 × L × I × R ≤ 3%
Example: 2,000 W geyser, 15 m: I = 8.7 A; 1.5 sq mm would carry it with 1.8% drop, but a geyser circuit is usually at least 2.5 sq mm, with a 10 A MCB.
Questions
What size wire for lights, sockets, AC and geyser?+
A common practice in Indian homes: 1.5 sq mm for lights and fans, 2.5 sq mm for 16 A power sockets and geysers, 4 sq mm for air conditioners. Long runs may need the next size up.
Why does the length of the wire matter?+
Longer wire has more resistance, so the voltage at the far end drops. Too much drop makes motors run hot and lights dim; a thicker wire fixes it.
Is the MCB supposed to protect the appliance?+
The MCB protects the wire. It must never be rated higher than the wire can safely carry.
Can I use aluminium wire instead?+
Aluminium carries less current than copper of the same size and its joints loosen over time. For house wiring, copper is the safe choice.